Troubleshooting Event Schemas
Troubleshooting Event Schemas Inconsistencies
If event schemas are consistent in the main system and subordinate system, in the Operation or Extended Operation tab, the property Event Schema Consistency Status of the System Settings node in the Operation or Extended Operation tab will indicate: No error.
In case of event schema inconsistencies between the configuration of the main system and the subordinate system an alarm occurs, and the property Event Schema Consistency Status will indicate one of the following error conditions:
Event Schema is missingInconsistent Discipline in Event MappingInconsistent Category in Event MappingInconsistent Alarm Class in Event MappingInconsistent Sound File in Event MappingInconsistent Color in Category MappingInconsistent Default Category in Category MappingInconsistent Category Identifier in Category MappingInconsistent Category Text in Category Mapping
Solution
- Export the library of the subject event schema belonging to the main system and then import it to the subordinate system.
Missing Event Categories in New Event Schema
After a change of Event Schema in the Events library, some event categories are missing in the lamps of the Summary bar.
Solution
If the Event Schema adds new event categories to the project, you must enable such new event categories in the Event Rights expander of the Security node:
- For all the required user groups scopes, configure the Event Rights of the new event categories as necessary for users to handle the events.
See Configuring Event Rights.